GCS low-voltage withdrawable switchgear

GCS low-voltage withdrawable switchgear is suitable for power distribution systems in power plants, petroleum, chemical, metallurgy, textiles, high-rise buildings and other industries. In large power plants, petrochemical systems and other places with high degree of automation and computer interface, it is used as a low-voltage complete power distribution device for power distribution, centralized motor control and reactive power compensation in power generation and power supply systems with three-phase AC frequency of 50(60)Hz, rated working voltage of 380V(400V),(660V) and rated current of 4000A and below.

Key words:

Classification:

Product Consulting:

Product Description

Product overview

GCS low-voltage withdrawable switchgear is suitable for power distribution systems in power plants, petroleum, chemical, metallurgy, textiles, high-rise buildings and other industries. In large power plants, petrochemical systems and other places with high degree of automation and computer interface, it is used as a low-voltage complete power distribution device for power distribution, centralized motor control and reactive power compensation in power generation and power supply systems with three-phase AC frequency of 50(60)Hz, rated working voltage of 380V(400V),(660V) and rated current of 4000A and below.

Model and meaning

GCS-□-□
G: Enclosed switchgear
C: withdrawal type
S: Electrical System
□: No. of main circuit scheme
□: No. of auxiliary circuit scheme

Conditions of use

◇ Ambient temperature: not higher than 40 ℃, not lower than -5 ℃; The average temperature within 24 hours shall not be 35 ℃; When exceeding, the operation shall be reduced according to the actual situation;
◇ Altitude: shall not exceed 2000m, for indoor use;
◇ Atmospheric conditions: the relative humidity of the surrounding air shall not exceed 50% at the highest temperature of +40 ℃, and a larger relative humidity shall be allowed at lower temperatures, such as 90% at +20 ℃. The influence of condensation due to temperature changes shall be considered;
◇ When the device is installed, the inclination of the vertical plane shall not exceed 50 ℃, and the whole group of cabinets shall be relatively flat (in line with the GBJ232-82 standard);
◇ The device should be installed in the place where there is no severe vibration and impact and it is not enough to make the electrical components not subject to corrosion;
Note:When ordering this product beyond the above conditions, please consult with our company.

performance index

The device is designed to meet the following criteria
◇ IEC439-1 low-voltage switchgear and control equipment;
◇ GB 7251 low voltage switchgear;
◇ ZBK 36001 low-voltage draw-out complete switchgear.

Basic technical parameters

Rated voltage of main circuit (V) AC 380(400), (660)
Rated voltage of auxiliary circuit (V) Alternating Current (AC)220, 380(400) Direct Current (DC)110, 220
Rated frequency (Hz) 50(60)
Rated insulation voltage (V) 660(1000)
Rated current (A) horizontal busbar ≤ 4000
Vertical busbar 1000
Rated short-time withstand current of busbar (kA,1s) 50,80
Rated peak withstand current of busbar (kA/0.1s) 105,176
Power frequency test voltage (V/1 min) main circuit 2500
auxiliary circuit 1760
Busbar three-phase four-wire system A.B.C.PE.N
three-phase 5 wire system A.B.C.PE.N
Protection level IP30.IP40

auxiliary circuit

The design of the auxiliary circuit diagram conforms to the "Technical Regulations on Power Consumption Design of Thermal Power Plants" and other relevant design technical regulations, and is applicable to the low-voltage plant (institute) power system of power plants and substations, and the low-voltage power distribution system in factories, mines, and high-rise buildings.
The auxiliary circuit scheme is designed according to the main circuit scheme divided into functional units of power supply incoming line, feeder (PC) and motor feeder (MCC) operation control.

main structure

◇ The main frame adopts 8MF type open section steel, and the two sides of the section steel have mounting holes with modulus of 20mm, 100mm and φ9.2mm respectively, so the internal installation is flexible and convenient;
◇ The main frame assembly form is designed for two kinds, fully assembled structure and part (side frame and beam) welded structure, for users to choose;
◇ The functional rooms of the device are isolated from each other, and the compartments are divided into functional unit room, bus room and cable room; the functions of each room are relatively independent;
◇ The horizontal main bus adopts the horizontal arrangement mode behind the cabinet to enhance the ability of the bus to resist electrodynamic force and make the main circuit of the device have the basic measures of high short-circuit strength;
◇ The design of the cable compartment makes it very convenient for the cables to enter and exit up and down.
◇ Dimension series of general cabinet of the device (see the following table):

High 2200
Wide 400 600 800 1000
Deep 800 1000 800 1000 600 800 1000 600 800 1000

recommend products

Get free product quotes

We will contact you within one working day. Please pay attention to your email.

Security verification
Submit immediately

Contact Us

img

Service Phone:

18309871229

img

Company Address

A005145 and A005146 Booth on the 5th Floor of Comprehensive Hall, No.10, Hunnan West Road, Hunnan District, Shenyang City

Powered by 300.cn

Business License